E2648-NH3-P


   Description

 

Ammonia transmitter E2618-NH3-P is a member of the PluraSens® family of multifunctional measurement instruments.

One of the most common applications is detection of explosive Ammonia concentrations in refrigeration machinery rooms.

The instrument utilizes a fully calibrated and temperature compensated pellistor (catalytic) gas sensor with excellent repeatability, stability and long lifetime.

Two relays with closing contact (optional) may be used for remote signaling or concentration control. Two alarm set-points are user settable.

Two analog outputs and RS485 digital interface with industry standard Modbus RTU protocol can be used to connect the detector to safety or building automation systems.

 

   Features
 
  • Stable long-life pellistor (catalytic bead) sensor
  • Range 0...15% vol. (0…100% LEL)
  • Resolution 0.1% vol. or 1% LEL
  • Two SPST relays option
  • 2 × 4-20 mA or 0-10 V, RS485
  • Attached or remote sensor
  • Industrial IP66 wall mount housing

 

   Specification

 

 

 

   Technical Data

 